ASS RCD does not trip

Views: 476

View statistics:

Past 24 Hours:
3
Past 7 Days:
13
Past 30 Days:
71
All Time:
476
Comments: 0

No one has left comments on this guide. Will you be first?

Go to guide comments
Completed: 0

No one has marked this guide "completed." Will you be the first?

Favorites: 0

No one has favorited (and subscribed to) this guide. Will you be the first?

Time Required: 30 minutes
Difficulty: Moderate
Featured Guide

This guide has been found to be exceptionally cool by the iFixit staff.

Community-Contributed Guide

An awesome member of our community made this guide. It was not created by iFixit staff.

ASS RCD does not trip

Introduction

Go to step 1 ↓

If you touch a live part and get an electric shock, the residual current device (RCD) detects it and switches off in a flash.

Having such a safety switch on your cable makes you feel safe (and rightly so), whether you're working on electronics or trimming your hedge.

It's just a problem if the protection fails at the critical moment......

What you need

Tools

    1. ASS RCD does not trip, unscrewing: step 1, image 1 of 1
      • the circuit breaker works with the IC RV4145, which requires 26V, but there are 230V on the line, the excess is 'burned off' in a large resistor

      • directly next to the resistor sits (stands) a small electrolytic capacitor, a design flaw, because electrolytic capacitors do not like heat ..... after a few years they are defective

      • and the dangerous thing here is, you don't notice anything ..... current still flows .......

      • Only by pressing the 'Test' button do you notice the defect!

      Ask FixBot

      Add Comment

    2. ASS RCD does not trip, Replace electrolytic capacitor: step 2, image 1 of 2 ASS RCD does not trip, Replace electrolytic capacitor: step 2, image 2 of 2
      • Desolder the defective electrolytic capacitor.

      • To make the new electrolytic capacitor last longer, install it on the underside... it is not as hot there.

      • Observe the polarity, see the photo for +.

      • When testing without switching off, the small test resistance can burn out and must then also be replaced; 6.8 kΩ for 30mA RCD (18 kΩ in the photo).

      Ask FixBot

      Add Comment

    3. ASS RCD does not trip, testing !: step 3, image 1 of 1
      • so, attention, such an RCD is not 'fail-safe'

      • therefore regularly press the 'Test' button !

      Ask FixBot

      Add Comment

Conclusion

Follow these steps in reverse order to reassemble your device.