ASS RCD does not trip

Views: 625

View statistics:

Past 24 Hours:
3
Past 7 Days:
20
Past 30 Days:
88
All Time:
625
Comments: 0

No one has left comments on this guide. Will you be first?

Go to guide comments
Completed: 0

No one has marked this guide "completed." Will you be the first?

Favorites: 0

No one has favorited (and subscribed to) this guide. Will you be the first?

Time Required: 30 minutes
Difficulty: Moderate
Featured Guide

This guide has been found to be exceptionally cool by the iFixit staff.

Community-Contributed Guide

An awesome member of our community made this guide. It was not created by iFixit staff.

ASS RCD does not trip

What you need

Tools

Introduction

Go to step 1 ↓

If you touch a live part and get an electric shock, the residual current device (RCD) detects it and switches off in a flash.

Having such a safety switch on your cable makes you feel safe (and rightly so), whether you're working on electronics or trimming your hedge.

It's just a problem if the protection fails at the critical moment......

    1. ASS RCD does not trip, unscrewing: step 1, image 1 of 1
      • the circuit breaker works with the IC RV4145, which requires 26V, but there are 230V on the line, the excess is 'burned off' in a large resistor

      • directly next to the resistor sits (stands) a small electrolytic capacitor, a design flaw, because electrolytic capacitors do not like heat ..... after a few years they are defective

      • and the dangerous thing here is, you don't notice anything ..... current still flows .......

      • Only by pressing the 'Test' button do you notice the defect!

      Ask FixBot

      Add Comment

    2. ASS RCD does not trip, Replace electrolytic capacitor: step 2, image 1 of 2 ASS RCD does not trip, Replace electrolytic capacitor: step 2, image 2 of 2
      • Desolder the defective electrolytic capacitor.

      • To make the new electrolytic capacitor last longer, install it on the underside... it is not as hot there.

      • Observe the polarity, see the photo for +.

      • When testing without switching off, the small test resistance can burn out and must then also be replaced; 6.8 kΩ for 30mA RCD (18 kΩ in the photo).

      Ask FixBot

      Add Comment

    3. ASS RCD does not trip, testing !: step 3, image 1 of 1
      • so, attention, such an RCD is not 'fail-safe'

      • therefore regularly press the 'Test' button !

      Ask FixBot

      Add Comment

Conclusion

Follow these steps in reverse order to reassemble your device.